Service neutral and "grounded conductor" sizing (2024)

L

lielec11

Senior Member
Location
Charlotte, NC
  • Tuesday at 10:40 AM
  • #1

I am having a discussion with an engineer regarding sizing the incoming service neutral to a service switch for a fire pump. Code dictates you need to run a neutral to the line side of the service switch, even if you do not need the neutral on the load side (i.e. a motor like a FP). Our disagreement stems on what section/table that should be used to size this neutral.

The engineer is pointing to NEC 250.24(C) which refers to "the grounded conductor brought to service equipment.", which then points to Table 250.66 for grounding electrode conductors.

I always thought the purpose to table 250.66 was to size GECs only, and that the service netural was the same size as the phase-conductors.

1) Is this a wrong assumption?
2) Is "grounded conductor" an AKA for a neutral?

I feel like all the neutrals I ever see are the same as the phase wires, not sized by Table 250.66.

roger

Moderator

Staff member

Location
Fl
Occupation
Retired Electrician
  • Tuesday at 10:44 AM
  • #2

"Grounded conductor" is the neutral and does not need to be the same size as the ungrounded conductors.

For sizing the "grounded conductor" see 220.61

roger

Moderator

Staff member

Location
Fl
Occupation
Retired Electrician
  • Tuesday at 10:48 AM
  • #3

BTW, the engineer is correct.

infinity

Moderator

Staff member

Location
New Jersey
Occupation
Journeyman Electrician
  • Tuesday at 10:51 AM
  • #4

lielec11 said:

I feel like all the neutrals I ever see are the same as the phase wires, not sized by Table 250.66.

Since there is no EGC ahead of the service disconnect the neutral needs to be large enough to clear a fault. As Roger said it does not need to be full size. In this case the fire pump doesn't require a neutral so it's brought to the service disconnect for fault clearing purposes.

L

lielec11

Senior Member
Location
Charlotte, NC
  • Tuesday at 11:20 AM
  • #5

roger said:

"Grounded conductor" is the neutral and does not need to be the same size as the ungrounded conductors.

For sizing the "grounded conductor" see 220.61

220.61 appears tp only apply to household ranges, etc. 220.61(B)(1) or specific electric systems like 3-wire DC, no? Or am I misreading that?

You also said they are correct, and I am leaning towards that as well, but you're both pointing to two different code sections. This engineer is using 250.66 to size the neutral (or grounded conductor in this case). In our case we have 750s AL so they're using a minimum of 3/0 AL neutral.

roger

Moderator

Staff member

Location
Fl
Occupation
Retired Electrician
  • Tuesday at 11:38 AM
  • #6

lielec11 said:

220.61 appears tp only apply to household ranges, etc. 220.61(B)(1) or specific electric systems like 3-wire DC, no? Or am I misreading that?

Even though 220.61 comes after 220.55 it is for the service as well as feeders.

220.61 Feeder or Service Neutral Load.

Read 250.24(C)(1) and you will see it takes you to 250.66.

L

lielec11

Senior Member
Location
Charlotte, NC
  • Tuesday at 11:43 AM
  • #7

I'm not sure where 220.55 came into play, was that a typo?

I did read 250.24(C)(1) and the reference to the Table 250.66. I guess my main question is where in the NEC does it link neutral conductor and "grounded" conductor? There is nothing in the definitions that states as much.

In regards to 220.61(B)(2) ... (because I don't think (B)(1) applies to fire pumps or any commercial loads) ... it references "...a portion of the unbalanced load in excess to 200A ..." How does that apply to a fire pump and how is the calculation done to prove the unbalanced current?

roger

Moderator

Staff member

Location
Fl
Occupation
Retired Electrician
  • Tuesday at 11:53 AM
  • #8

lielec11 said:

I'm not sure where 220.55 came into play, was that a typo?

No it wasn't a TYPO you said you thought 220.61 was referring to household ranges and since 220.61 comes right after household ranges (220.55) it seemed as though that had you confused.

As far as the neutral being the grounded conductor, the NEC is not an instruction manual, it does not need to define every item but read the title of article 200.

ARTICLE 200
Use and Identification of Grounded
Conductors

L

lielec11

Senior Member
Location
Charlotte, NC
  • Tuesday at 12:10 PM
  • #9

Thanks for the guidance to section 200, definitely an overlooked part of my code book.

The last open item is in regards to 220.61(B)(2). I don't see how this applies to, or how to implement it, for a fire pump load. I still think the proper way is how the engineer in my original post sized it, using 250.24(C)(1) and Table 250.66.

roger

Moderator

Staff member

Location
Fl
Occupation
Retired Electrician
  • Tuesday at 12:18 PM
  • #10

lielec11 said:

Thanks for the guidance to section 200, definitely an overlooked part of my code book.

The last open item is in regards to 220.61(B)(2). I don't see how this applies to, or how to implement it, for a fire pump load. I still think the proper way is how the engineer in my original post sized it, using 250.24(C)(1) and Table 250.66.

I see my post sending you to 220.61 could be confusing, it was meant to point out that the neutral does not have to always be the same size as the ungrounded conductors. With that said I agree the engineer is on top of things.

L

lielec11

Senior Member
Location
Charlotte, NC
  • Tuesday at 12:19 PM
  • #11

roger said:

I see my post sending you to 220.61 could be confusing, it was meant to point out that the neutral does not have to always be the same size as the ungrounded conductors. With that said I agree the engineer is on top of things.

I understand, thanks for sticking with me through this little discussion!

roger

Moderator

Staff member

Location
Fl
Occupation
Retired Electrician
  • Tuesday at 12:20 PM
  • #12

lielec11 said:

I understand, thanks for sticking with me through this little discussion!

You're welcome.

You must log in or register to reply here.

Service neutral and "grounded conductor" sizing (2024)

References

Top Articles
Europe : comment profiter d’un voyage en train à prix réduit ? 
Via Rail Train Tickets, Schedules and Fares
Ups Notary Store Near Me
サリスF70プッシュへのプッシュフルエクステンションヘビーデューティドロワーランナー
glizzy - Wiktionary, the free dictionary
Mashle: Magic And Muscles Gogoanime
Lkq Pull-A-Part
Busted Newspaper Longview Texas
Matka 786 Guessing
Fatshark Forums
Join MileSplit to get access to the latest news, films, and events!
How To Find IP Address From Discord | ITGeared
Craigslist Free En Dallas Tx
How to find cash from balance sheet?
Dr Bizzaro Bubble Tea Menu
Trizzle Aarp
Fit 4 Life Murrayville Reviews
Gopher Hockey Forum
Ofw Pinoy Channel Su
Spirited Showtimes Near Gqt Kalamazoo 10
عکس کون زنان ایرانی
Samanthaschwartz Fapello
Tiffin Ohio Craigslist
Craigs List Duluth Mn
Sugar And Spice Playboy Magazine
Natasha Tillotson
Dr. Nicole Arcy Dvm Married To Husband
Q Zangle Cvusd
Closest Dollar Tree Store To My Location
19 Dollar Fortnite Card Copypasta
Myhr.bannerhealth.com
Baby | Voeding | Voeding het eerste jaar; borstvoeding
Arapahoe Youth League Baseball
Think Up Elar Level 5 Answer Key Pdf
Island Photography Discount Code
Refinery29 Horoscopes
Auto Next, 2496 Mount Moriah Rd, Memphis, TN 38115, US - MapQuest
Lactobacillus reuteri : présentation, bienfaits et avis sur ce probiotique
Skip The Games Albany
Fuzz Bugs Factory Number Bonds
Chloe Dicarlo
Sacramento Library Overdrive
Dr Ommert Norwalk Ohio
Exploring The Craigslist Washington DC Marketplace - A Complete Overview
Greenville Sc Greyhound
Uk Pharmacy Turfland
Calliegraphics
Select Costco Stores: Insta360 X3 5.7K 360° Action Camera Adventure Bundle $100 (In-Store Purchase Only)
Fired Up | Rotten Tomatoes
Carenow Urgent Care - Eastchase Fort Worth Photos
Job ID:24023861 - Compliance and Operational Risk Specialist - Multiple Locations
What Does Code 898 Mean On Irs Transcript
Latest Posts
Article information

Author: Aracelis Kilback

Last Updated:

Views: 5924

Rating: 4.3 / 5 (44 voted)

Reviews: 83% of readers found this page helpful

Author information

Name: Aracelis Kilback

Birthday: 1994-11-22

Address: Apt. 895 30151 Green Plain, Lake Mariela, RI 98141

Phone: +5992291857476

Job: Legal Officer

Hobby: LARPing, role-playing games, Slacklining, Reading, Inline skating, Brazilian jiu-jitsu, Dance

Introduction: My name is Aracelis Kilback, I am a nice, gentle, agreeable, joyous, attractive, combative, gifted person who loves writing and wants to share my knowledge and understanding with you.